We are looking for programmable setback thermostats for our radiant
hot water heating system in our building.
Freeze control is the real driving requirement, as the rads are on the
outside cold wall of the units, and have a tendancy to freeze solid
with the resulant mess in winter.

To prevent that, a program that temporarily cycles the heat on is
needed (for instance 1 out of every 30 minutes), in addition to the
normal freeze control program that is based on ambient air temp. The
heater control is a normally closed (NC) circuit, where an open
circuit causes the valve to open and hot water to circulate.

Can anyone point me to programmable thermostats with all of these
features?

Any help much appreciated.

Barry

Archived from group: alt>hvac
Back to top
View user's profile Send private message
geothermaljones



Joined: 07 Aug 2007
Posts: 47

PostPosted: Tue Feb 26, 2008 9:53 pm    Post subject: Re: setback thermostat with freeze protection program Reply with quote

Never cared much for setback stats on scorched air units, but on radiators
they don't seem to make any sense at all.
How far down is your setback point that allows the units to freeze?
Do you have a stat & control for each radiator, or one for a number of
different spaces?
It'd make some sense to put a pump exerciser on the circ pump & have it run
for a minute every 15, 30, or 60 minutes just to move some water through...
I think your problem has little to do with the stats.

goodluck
geothermaljones



wrote in message@34g2000hsz.googlegroups.com...
> We are looking for programmable setback thermostats for our radiant
> hot water heating system in our building.
> Freeze control is the real driving requirement, as the rads are on the
> outside cold wall of the units, and have a tendancy to freeze solid
> with the resulant mess in winter.
>
> To prevent that, a program that temporarily cycles the heat on is
> needed (for instance 1 out of every 30 minutes), in addition to the
> normal freeze control program that is based on ambient air temp. The
> heater control is a normally closed (NC) circuit, where an open
> circuit causes the valve to open and hot water to circulate.
>
> Can anyone point me to programmable thermostats with all of these
> features?
>
> Any help much appreciated.
>
> Barry
Back to top
View user's profile Send private message
Tom Beckner



Joined: 27 Jan 2008
Posts: 5

PostPosted: Wed Feb 27, 2008 4:15 am    Post subject: Re: setback thermostat with freeze protection program Reply with quote

wrote in message @34g2000hsz.googlegroups.com...

> We are looking for programmable setback thermostats for our radiant
> hot water heating system in our building.

That's an off the shelf deal from your local supply house.

> Freeze control is the real driving requirement, as the rads are on the
> outside cold wall of the units, and have a tendancy to freeze solid
> with the resulant mess in winter.

Ok.

> To prevent that, a program that temporarily cycles the heat on is
> needed (for instance 1 out of every 30 minutes), in addition to the
> normal freeze control program that is based on ambient air temp.

The direct approach is maintain a space temperature via your
new thermostat when the zone is unoccupied, 60 F or whatever
depending on your application.

> ... The heater control is a normally closed (NC) circuit, where
> an open circuit causes the valve to open and hot water to circulate.

The "fail safe" convention is to use NO valves for heat.

An outdoor thermostat brings on the pump, when unoccupied, at nominal 40 F,
giving freeeze protection when using NO valves. But could still be used
with
your NC deal in the short term as long as the setback thermostats and
everything
else in the control loop is working.

In addition, the convention is to reset the water temperature, basis an
outdoor
thermostat, with a three way diverting valve at the boiler. Your building
may
or may not already have that.

Your best bet is to go to a local supply house and briefly discuss your
problem. Ask them to recommend a local mechanic or contractor that can
come out and set the job up for you.

I could be wrong.

Tom Beckner
Back to top
View user's profile Send private message
bbortnick



Joined: 26 Feb 2008
Posts: 4

PostPosted: Wed Feb 27, 2008 1:36 pm    Post subject: Re: setback thermostat with freeze protection program Reply with quote

Thanks all for your responses;
The circulating pump runs at all times, the local thermostat/valve
allowing the hot water to route through the rads along the outside
walls. The abient air temp may still be high (higher than the normal
freeze protection temp) while the rad next to the wall experiences
much colder temps and is thus subject to freezing.

These are all individual apartments, with the occupants setting their
own temperatures, perhaps even leaving them off in the winter if heat
from other units is enough, and/or leaving windows open in the winter
(freezing air dropping down over the window sill onto the pipes)
setting the stage for burst pipes.


The thermostat needs to compensate for the poor actions of tenants.
Back to top
View user's profile Send private message
Stormin Mormon



Joined: 07 Aug 2007
Posts: 284

PostPosted: Wed Feb 27, 2008 9:11 pm    Post subject: Re: setback thermostat with freeze protection program Reply with quote

I dare say your last sentence says it all. The thermostat is asked to
compensate for the actions of tenants.

A thermostat that calls for heat 30 seconds on the quarter hour would sure
help keep the pipes from freezing.

--
Christopher A. Young
Learn more about Jesus
www.lds.org
..


wrote in message @d5g2000hsc.googlegroups.com...
Thanks all for your responses;
The circulating pump runs at all times, the local thermostat/valve
allowing the hot water to route through the rads along the outside
walls. The abient air temp may still be high (higher than the normal
freeze protection temp) while the rad next to the wall experiences
much colder temps and is thus subject to freezing.

These are all individual apartments, with the occupants setting their
own temperatures, perhaps even leaving them off in the winter if heat
from other units is enough, and/or leaving windows open in the winter
(freezing air dropping down over the window sill onto the pipes)
setting the stage for burst pipes.


The thermostat needs to compensate for the poor actions of tenants.

Back to top
View user's profile Send private message
Display posts from previous:   
Post new topic   Reply to topic    hvacfreaks.com Forum Index -> HVAC General All times are GMT
Page 1 of 1

 
Jump to:  
You cannot post new topics in this forum
You cannot reply to topics in this forum
You cannot edit your posts in this forum
You cannot delete your posts in this forum
You cannot vote in polls in this forum


Powered by phpBB © 2001, 2005 phpBB Group