Marc O'Brien
Joined: 23 Jan 2008 Posts: 91
|
Posted: Tue Feb 26, 2008 1:32 am Post subject: Re: Actually, it could be a volumetrically compromised compr |
|
|
On Feb 26, 2:29 am, "Zyp" wrote:
> Tony wrote:
> > Taken in consideration what stormin and zyp told you
> > I believe that EPR valve are still being made
> > tony
>
> > "B-Hate-Me" wrote in message
> >@comcast.com...
>
> >> "Marc O'Brien" wrote in message
> >>@s37g2000prg.googlegroups.com....
> >>> I poped back in to see how this cellar cooler system was doing after
> >>> my repairs.
>
> >>> It's iced again but this time the full charge still exists, subcool
> >>> remains sufficient.
>
> >>> It's design saturated evaporating temperature is about 4 deg C,
> >>> however, surely, due to an inefficient compressor the lower
> >>> evaporator circuit freezes?
>
> >> Add a hot gas bypass and solenoid.
>
> For the first time in how many month's, I actually understood what Tony
> said. An EPR valve might help here.
>
> --
> Zyp- Hide quoted text -
An EPR would further reduce the turbulance in the distributor which
would only worsen the scenario I have shared in a previous post.
Archived from group: alt>hvac |
|
| Back to top |
|
 |
Marc O'Brien
Joined: 23 Jan 2008 Posts: 91
|
Posted: Tue Feb 26, 2008 1:44 am Post subject: Re: Actually, it could be a volumetrically compromised compr |
|
|
On Feb 26, 3:30 am, .p.jm@see_my_sig_for_address.com wrote:
> On Mon, 25 Feb 2008 18:29:59 -0800, "Zyp" wrote:
> >Tony wrote:
> >> Taken in consideration what stormin and zyp told you
> >> I believe that EPR valve are still being made
> >> tony
>
> >> "B-Hate-Me" wrote in message
> >>@comcast.com...
>
> >>> "Marc O'Brien" wrote in message
> >>>@s37g2000prg.googlegroups.com....
> >>>> I poped back in to see how this cellar cooler system was doing after
> >>>> my repairs.
>
> >>>> It's iced again but this time the full charge still exists, subcool
> >>>> remains sufficient.
>
> >>>> It's design saturated evaporating temperature is about 4 deg C,
> >>>> however, surely, due to an inefficient compressor the lower
> >>>> evaporator circuit freezes?
>
> >>> Add a hot gas bypass and solenoid.
>
> >For the first time in how many month's, I actually understood what Tony
> >said. An EPR valve might help here.
>
> At the risk of short cycling. I always hesitate to look at
> 'solutions' that involve re-engineering the system.
Indeed, keep it simple stupid. The irony is that one has to know an
aweful lot more each time one wants to further simplify something.
Like the saying "Sorry my letter to you is so long but I didn't have
the time to write a shorter one".
An EPR reduces evaporator volume flow which is precisely not what you
want if your problem is already too little evaporator volume flow. |
|
| Back to top |
|
 |
.p.jm
Joined: 07 Aug 2007 Posts: 527
|
Posted: Tue Feb 26, 2008 3:30 am Post subject: Re: Actually, it could be a volumetrically compromised compr |
|
|
On Mon, 25 Feb 2008 18:29:59 -0800, "Zyp" wrote:
>Tony wrote:
>> Taken in consideration what stormin and zyp told you
>> I believe that EPR valve are still being made
>> tony
>>
>>
>> "B-Hate-Me" wrote in message
>> @comcast.com...
>>>
>>> "Marc O'Brien" wrote in message
>>> @s37g2000prg.googlegroups.com...
>>>> I poped back in to see how this cellar cooler system was doing after
>>>> my repairs.
>>>>
>>>> It's iced again but this time the full charge still exists, subcool
>>>> remains sufficient.
>>>>
>>>> It's design saturated evaporating temperature is about 4 deg C,
>>>> however, surely, due to an inefficient compressor the lower
>>>> evaporator circuit freezes?
>>>
>>> Add a hot gas bypass and solenoid.
>
>For the first time in how many month's, I actually understood what Tony
>said. An EPR valve might help here.
At the risk of short cycling. I always hesitate to look at
'solutions' that involve re-engineering the system.
--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/
Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/ |
|
| Back to top |
|
 |
Zyp
Joined: 22 Aug 2007 Posts: 275
|
Posted: Wed Feb 27, 2008 2:04 pm Post subject: Re: Actually, it could be a volumetrically compromised compr |
|
|
Marc O'Brien wrote:
> On Feb 26, 3:30 am, .p.jm@see_my_sig_for_address.com wrote:
>> On Mon, 25 Feb 2008 18:29:59 -0800, "Zyp" wrote:
>>> Tony wrote:
>>>> Taken in consideration what stormin and zyp told you
>>>> I believe that EPR valve are still being made
>>>> tony
>>
>>>> "B-Hate-Me" wrote in message
>>>> @comcast.com...
>>
>>>>> "Marc O'Brien" wrote in message
>>>>> @s37g2000prg.googlegroups.com...
>>>>>> I poped back in to see how this cellar cooler system was doing
>>>>>> after my repairs.
>>
>>>>>> It's iced again but this time the full charge still exists,
>>>>>> subcool remains sufficient.
>>
>>>>>> It's design saturated evaporating temperature is about 4 deg C,
>>>>>> however, surely, due to an inefficient compressor the lower
>>>>>> evaporator circuit freezes?
>>
>>>>> Add a hot gas bypass and solenoid.
>>
>>> For the first time in how many month's, I actually understood what
>>> Tony said. An EPR valve might help here.
>>
>> At the risk of short cycling. I always hesitate to look at
>> 'solutions' that involve re-engineering the system.
>
> Indeed, keep it simple stupid. The irony is that one has to know an
> aweful lot more each time one wants to further simplify something.
> Like the saying "Sorry my letter to you is so long but I didn't have
> the time to write a shorter one".
>
> An EPR reduces evaporator volume flow which is precisely not what you
> want if your problem is already too little evaporator volume flow.
I'm not sure his problem stems from evaporator flow. It seems to me that
when the fixture temperature is just above freeze point, and the evaporator
is below freeze point, you're getting frost no matter what you do. At least
an EPR could keep the evaporator from reaching that point. [Albeit - it is
already a case of refrigeration effect being lost because of the saturation
temperature and flow.] Perhaps just simply execute a defrost every 3-4
hours for 20 minutes would be sufficient. It depends on his load for the
fixture, no?
--
Zyp |
|
| Back to top |
|
 |
Marc O'Brien
Joined: 23 Jan 2008 Posts: 91
|
Posted: Wed Feb 27, 2008 8:05 pm Post subject: Re: Actually, it could be a volumetrically compromised compr |
|
|
On Feb 27, 5:04 pm, "Zyp" wrote:
> Marc O'Brien wrote:
> > On Feb 26, 3:30 am, .p.jm@see_my_sig_for_address.com wrote:
> >> On Mon, 25 Feb 2008 18:29:59 -0800, "Zyp" wrote:
> >>> Tony wrote:
> >>>> Taken in consideration what stormin and zyp told you
> >>>> I believe that EPR valve are still being made
> >>>> tony
>
> >>>> "B-Hate-Me" wrote in message
> >>>>@comcast.com...
>
> >>>>> "Marc O'Brien" wrote in message
> >>>>>@s37g2000prg.googlegroups.com...
> >>>>>> I poped back in to see how this cellar cooler system was doing
> >>>>>> after my repairs.
>
> >>>>>> It's iced again but this time the full charge still exists,
> >>>>>> subcool remains sufficient.
>
> >>>>>> It's design saturated evaporating temperature is about 4 deg C,
> >>>>>> however, surely, due to an inefficient compressor the lower
> >>>>>> evaporator circuit freezes?
>
> >>>>> Add a hot gas bypass and solenoid.
>
> >>> For the first time in how many month's, I actually understood what
> >>> Tony said. An EPR valve might help here.
>
> >> At the risk of short cycling. I always hesitate to look at
> >> 'solutions' that involve re-engineering the system.
>
> > Indeed, keep it simple stupid. The irony is that one has to know an
> > aweful lot more each time one wants to further simplify something.
> > Like the saying "Sorry my letter to you is so long but I didn't have
> > the time to write a shorter one".
>
> > An EPR reduces evaporator volume flow which is precisely not what you
> > want if your problem is already too little evaporator volume flow.
>
> I'm not sure his problem stems from evaporator flow. It seems to me that
> when the fixture temperature is just above freeze point, and the evaporator
> is below freeze point, you're getting frost no matter what you do. At least
> an EPR could keep the evaporator from reaching that point. [Albeit - it is
> already a case of refrigeration effect being lost because of the saturation
> temperature and flow.] Perhaps just simply execute a defrost every 3-4
> hours for 20 minutes would be sufficient. It depends on his load for the
> fixture, no?
I have a full charge but I am not getting even frosting. The room
temperature at the time of frosting was 16°C.
I happen to be popping in again tomorrow for another un-related reason
and will experiment further.
|
|
| Back to top |
|
 |
|
|
|