PostPosted: Fri Feb 15, 2008 10:27 pm    Post subject: air source heat pump, split system, supply water for slab he Reply with quote

I'm wondering if anyone can offer some advice on the best approach to
get hot water for slab heating (say, 25C) in winter, and chilled water
for dehumidication and slight slab chilling in the summer from an air
source heat pump. The project is a small (10,000 sq.ft.) commercial
building. We'd be best to size off of chilling capacity of 25 tons,
which will require some supplemental heat (likely oil-fired boiler) as
heating exceeds cooling in our climate. Anyway my problem is that the
project's HVAC engineer has experience only with air source heat pumps
that connect to air handling units and is a loss as to what to connect
to generate heated/cooled water. I'd appreciate any direction.

Archived from group: alt>hvac
Back to top
View user's profile Send private message
Noon-Air



Joined: 07 Aug 2007
Posts: 363

PostPosted: Sat Feb 16, 2008 3:46 am    Post subject: Re: air source heat pump, split system, supply water for sla Reply with quote

"Fred" wrote in message @s37g2000prg.googlegroups.com...
> I'm wondering if anyone can offer some advice on the best approach to
> get hot water for slab heating (say, 25C) in winter, and chilled water
> for dehumidication and slight slab chilling in the summer from an air
> source heat pump. The project is a small (10,000 sq.ft.) commercial
> building. We'd be best to size off of chilling capacity of 25 tons,
> which will require some supplemental heat (likely oil-fired boiler) as
> heating exceeds cooling in our climate. Anyway my problem is that the
> project's HVAC engineer has experience only with air source heat pumps
> that connect to air handling units and is a loss as to what to connect
> to generate heated/cooled water. I'd appreciate any direction.

You really need to re-think the idea of chilling the slab in summer....
think "dew point"
Back to top
View user's profile Send private message
.p.jm



Joined: 07 Aug 2007
Posts: 527

PostPosted: Sat Feb 16, 2008 5:04 am    Post subject: Re: air source heat pump, split system, supply water for sla Reply with quote

On Fri, 15 Feb 2008 17:27:15 -0800 (PST), Fred
wrote:

>I'm wondering if anyone can offer some advice on the best approach to
>get hot water for slab heating (say, 25C) in winter, and chilled water
>for dehumidication and slight slab chilling in the summer from an air
>source heat pump. The project is a small (10,000 sq.ft.) commercial
>building. We'd be best to size off of chilling capacity of 25 tons,
>which will require some supplemental heat (likely oil-fired boiler) as
>heating exceeds cooling in our climate. Anyway my problem is that the
>project's HVAC engineer has experience only with air source heat pumps
>that connect to air handling units and is a loss as to what to connect
>to generate heated/cooled water. I'd appreciate any direction.

It's called a flat plate heat exchanger. It would simply go
where the indoor coil is now.

http://www.flatplate.org is one source.

I'd recommend he get experienced design help, you don't just
turn the unit on and off like you do in an air handler system. You
need a buffer tank.

As Noon said, do not cool the slab unless you pay close
attention to dewpoint - dew / mold issues.


--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/
Back to top
View user's profile Send private message
geothermaljones



Joined: 07 Aug 2007
Posts: 47

PostPosted: Sat Feb 16, 2008 1:59 pm    Post subject: Re: air source heat pump, split system, supply water for sla Reply with quote

There are a large number of water heating HP's, most are marketed as pool
heaters.
Google should find a bunch...
I'm not sure you'll find an Air to water heatpump that chills water...
but if you do, let me know.
Take care with water treatment chemicals & how the heat pump performs,
although if they're built for
chlorinated pool water, they'll probably handle anything your system will
use.
Have your engineer plot the wet bulb temps on a Psych Chart before you cool
your slab.
Unless your in the dessert or high in the mountains you'll have a wet
floor...
I believe Dew Point was mentioned earlier.

goodluck
geothermaljones
st.paul,mn



"Fred" wrote in message@s37g2000prg.googlegroups.com...
> I'm wondering if anyone can offer some advice on the best approach to
> get hot water for slab heating (say, 25C) in winter, and chilled water
> for dehumidication and slight slab chilling in the summer from an air
> source heat pump. The project is a small (10,000 sq.ft.) commercial
> building. We'd be best to size off of chilling capacity of 25 tons,
> which will require some supplemental heat (likely oil-fired boiler) as
> heating exceeds cooling in our climate. Anyway my problem is that the
> project's HVAC engineer has experience only with air source heat pumps
> that connect to air handling units and is a loss as to what to connect
> to generate heated/cooled water. I'd appreciate any direction.
Back to top
View user's profile Send private message
Bob Pietrangelo



Joined: 07 Aug 2007
Posts: 55

PostPosted: Sat Feb 16, 2008 4:40 pm    Post subject: Re: air source heat pump, split system, supply water for sla Reply with quote

>
> You really need to re-think the idea of chilling the slab in summer....
> think "dew point"
>

Steve,

With proper dehumidification it is easily done. I wouldn't do it up my way,
or down in your neck of the woods with out dehumidifacation, but in really
dry climates it is really starting to come into vogue.

This guy needs a HVAC com, or engineer versed in GEO.
Back to top
View user's profile Send private message
becauseofjunk



Joined: 11 Feb 2008
Posts: 12

PostPosted: Sat Feb 16, 2008 8:32 pm    Post subject: Re: air source heat pump, split system, supply water for sla Reply with quote

Condensation in slab is a major concern, and the dehumidification
system may not compensate.

And I do agree with Bob, there are plenty of geo companies out there
willing to do the engineering for you (but they are selling their
product). The Litmus test comes down to climate, energy management
and how much your IAQ is going to suffer. You would need heat
recovery or fresh air intake.

Maybe because I live in a rain forest...just wouldn't do it..no way.
Use a HP??? Boy, I do have some other ideas I have been thinking up.
Would anyone like to start a thread on "theory"???

Where I am now: Need ductwork, heatpump and ERV to serve IAQ
requiriements and local codes on mild load days (assuming best case
Manual J scenerio). Boiler for supplemental heat in slab, using a hi
effic condensing boiler, Because slab heat runs at lower temps
without mixing valves or bypass pump. You can cool slab with heat
pump in dry climate but ...I just am not too sure if willing to loose
my IAQ, have wet carpet, have slip and falls on tile or
concrete...Obviously, I do not know what purpose this space is to be
used as or where?
Back to top
View user's profile Send private message
Jeffrey Lebowski



Joined: 14 Jan 2008
Posts: 15

PostPosted: Sat Feb 16, 2008 11:30 pm    Post subject: Re: air source heat pump, split system, supply water for sla Reply with quote

"geothermaljones" wrote in message@comcast.com...
> There are a large number of water heating HP's, most are marketed as pool
> heaters.
> Google should find a bunch...
> I'm not sure you'll find an Air to water heatpump that chills water...
> but if you do, let me know.

http://www.poolsaz.com/ProductDetails.asp?ProductCode=AE3000TR&click=1271

> Take care with water treatment chemicals & how the heat pump performs,
> although if they're built for
> chlorinated pool water, they'll probably handle anything your system will
> use.
> Have your engineer plot the wet bulb temps on a Psych Chart before you
cool
> your slab.
> Unless your in the dessert or high in the mountains you'll have a wet
> floor...
> I believe Dew Point was mentioned earlier.
>

--

Back to top
View user's profile Send private message
Display posts from previous:   
Post new topic   Reply to topic    hvacfreaks.com Forum Index -> HVAC General All times are GMT
Page 1 of 1

 
Jump to:  
You cannot post new topics in this forum
You cannot reply to topics in this forum
You cannot edit your posts in this forum
You cannot delete your posts in this forum
You cannot vote in polls in this forum


Powered by phpBB © 2001, 2005 phpBB Group